БДС EN IEC 61472-2:2021

Live working - Minimum approach distances - Part 2: Method of determination of the electrical component distance for AC systems from 1,0 kV to 72,5 kV

Aug 16, 2021

General information

60.60     Aug 16, 2021

BDS

ТК-79

European Standard

13.26     29.240.99     29.260.99     13.260  

English  

Buying

Published

Language in which you want to receive the document

Scope

IEC 61472-2:2021 specifies a method for determining the electrical component of the minimum approach distances for live working, for AC systems 1 kV up to and including 72,5 kV. This document addresses system overvoltages and the working air distances between equipment and/or workers at different potentials.

The withstand voltage and minimum approach distances determined by the method described in this document can be used only if the following working conditions prevail:
<ul>
<li>workers are trained for, and skilled in, working live lines or close to live conductors or equipment;</li>
<li>the operating conditions are adjusted so that the statistical overvoltage does not exceed the value selected for the determination of the required withstand voltage;</li>
<li>transient overvoltages are the determining overvoltages;</li>
<li>tool insulation has no continuous film of moisture present on the surface;</li>
<li>no lightning is observed within 10 km of the work site;</li>
<li>allowance is made for the effect of the conducting components of tools.</li>